Newly redesigned MSCT Series »

Thermistors Flush Mount

This product is covered by ACI's Five (5) Year Limited Warranty. Learn more

Product overview

1,800 Ohm Thermistor, Flush Mount Button, Plastic

Application

  • Museums
  • Historical Buildings
  • Monitoring Space Temperatures
  • Office Buildings
  • Schools
  • Retail
  • Remote Sensor

Product specifications

Sensor Type | Sensor Curve:
Thermistor | Non-Linear, NTC (Negative Temperature Coefficient)
Number Sensing Points:
One
Number Wires:
Two (Non-Polarity Sensitive)
Sensor Output @ 25ºC (77ºF):
A/1.8K: 1.8KΩ nominal | (Red/Yellow) A/10KS: 10KΩ nominal | (White/Blue) A/3K: 3KΩ nominal | (White/Brown) A/10K-E1: 10KΩ nominal | (Gray/Orange) A/AN (Type III): 10KΩ nominal | (White/White) A/20K: 20KΩ nominal | (Brown/Blue) A/AN-BC: 5.238KΩ nominal | (White/Yellow) A/50K: 50KΩ nominal | (Brown/Yellow) A/CP (Type II): 10KΩ nominal | (White/Green) A/100KS: 100KΩ nominal | (Black/Yellow) A/CSI: 10KΩ nominal | (Green/Yellow)
Accuracy 0-70ºC (32-158ºF):
+/-0.2°C (+/-0.36°F) except A/10K-E1 Series: +/-0.3°C (+/-0.54°F) A/1.8K Series: +/-0.5°C @ 25°C (77°F) and (+/-1.0°C) (+/-1.8°F)
Response Time (63% Step Change):
10 Seconds nominal
Power Dissipation Constant:
3 mW/°C except A/1.8K Series: 1 mW/°C | A/10K-E1 Series: 2 mW/°C
Enclosure Material:
A/XX-BBS Series: Brass | A/XX-SBS Series: 304 Stainless Steel | A/XX-PBS Series: ABS
Enclosure Flammability Rating:
UL94-HB
Operating Temperature Range:
A/XX-PBS Series: -40 to 70°C (-40 to 158°F) A/XX-BBS & A/XX-SBS Series: -40 to 150°C (-40 to 302°F)
Operating Humidity Range:
10 to 95% RH, non-condensing
Lead Length | Conductor Size:
24” (61cm) | 22 AWG (0.65mm)
Lead Wire Insulation | Wire Rating:
Etched Teflon (PTFE) Colored Leads | Mil Spec 16878/4 Type E)
Conductor Material:
Silver Plated Copper
Product Dimensions:
A/XX-PBS Series: 1.00” (25.4mm) x 0.750” (19mm) A/XX-BBS and A/XX-SBS Series: 1.20” (30.48mm) x 0.700” (17.78mm)
Product Weight:
A/XX-PBS Series: 0.04 lbs. (18.15g) | A/XX-BBS & A/XX-SBS Series: 0.10 lbs. (45.36g)
Agency Approvals:
CE, RoHS2, WEEE