Selectable Analog to Pressure Transducers

Product Data

ACI/EPC Series

Product Description

The ACI/EPC converts an analog input signal into a proportional pneumatic output . The output pressure ranges are jumper selectable for 0-10, 0-15 and 0-20 psi and are adjustable in all ranges. The EPC will automatically modulate its' control valve to control the branch line pressure to the selected setpoint as determined by the input signal. The input signal may be either a 0 to 5, 0 to 10, 0 to 15,VDC or a 4 to 20 mA signal.

Another notable feature of the EPC is that it has an adjustable, manual override potentiometer that can be used to increase or decrease the pneumatic output. A manual override feedback signal of a N/O dry contact rated for 1A @ 24 VAC/DC is also available on all of the EPC units. An LED is also supplied for power indication. All EPC's contain a 0 to 5VDC feedback signal that may be used to monitor the branch line pressure.

The EPC is a single valve constant bleed controller with branch response times determined by the .007" orifice.

Both the EPC2 and EPC2FS incorporate two valves and are not constant bleed controls. Their branch exhaust flow and response times are similar to its load rate. For optimum operation it is recommended to have a branch line with a minimum 25 feet of 1/4" O.D. tubing. 

If power is lost to the EPC2, it will not exhaust any additional air from the branch line as long as there is not a leak. Whereas the EPC and EPC2FS will bleed air until the branch line pressure is equal to 0 PSI.

Some of the most common applications for the ACI/EPC's are:

  • Valve and Damper Actuator Controls

  • Fan Vane Control

  • Pilot Positioner Control

  • Chiller Loading

  • DDC Control

All of these units come with a two year factory warranty. Please contact ACI for more information regarding any of these products.

 

Product Specifications

Supply Voltage

24 VDC + 10% -5%
24 VAC +/- 10%

Supply Pressure

25 psi min, must be 2 psi above max output pressure.

Output Pressure

0 to 10, 0-15, or 0-20 psi

Analog Input Ranges

0-5, 0-10, 0-15, or 0-20mA

Feedback Output

0 to 5 VDC

Operating Temp Range

32 to 120oF

Supply Current

180 mA Max

Operating RH

5 to 95% RH non-condensing

Accuracy

+/- 1% FS @ Room Temp
+/- 3% FS over Operating Temp

Input Impedance

Voltage Input =  Infinite Ohms
Current Input = 250 Ohms

Dimensions

Ordering Information

Valve Type Program- Rate of Change Gauge Enclosure
A/EPC [  ] [  ] [  ]  [  ]
( ) .007" Orifice (41 scim +/- 5%) (  ) No Gauge (Std) (  ) No Enclosure (Std)
(2) No Bleed (750 scim supply and exhaust) (G) With Gauge (ENC1) With Enclosure
(2FS) No Bleed (750 scim supply and exhaust)
4

Example: A/EPC2-G     or     A/EPC     or     A/EPC2FS-G-ENC1