Pressure to Current Transducer

Product Data

ACI/PTP

Product Description

The ACI/PTP will accept either a 0 to -7.5, 3 to 15, or 3 to 30 psig pneumatic input and convert it into a proportional 4 to 20 mA current output.  By adding one of the supplied external load resistors, the ACI/PTP will output a proportional 1 to 5, 2 to 10, or 3 to 15 VDC signal.  It is a positive current output device that is fully temperature compensated. 

Some of the most common applications for the ACI/PTP are:

·         Building Automation
·         Process Control
·         Pneumatic System Monitoring
·         Pneumatic to Proportional Analog 
      Output

A plugged 1/8”-27 FNPT gauge port is included for local mechanical indication.  The ACI/PTP is available in a 2.25” snap track mount configuration and is designed to accept a standard ¼” O.D. plastic tubing. 

The ENC1, is a compact metal enclosure, with a light gray powder coat finish.  A 2” diameter opening in the cover will enable you to view the gauge.  Two 7/8” diameter openings in the base ends can be used for ½” EMT conduit fittings.  All  mounting hardware for the interface device is included along with (3) plastic covers for covering both the gauge opening and the (2) 7/8” diameter knockouts.

All units have a two year warranty.  Contact ACI for further information regarding this product. 

Product Specifications

Supply Voltage

Regulated 22.6 to 26.4 VDC

Supply Pressure

15 psig max  (PTP 3 to 15)

 

Regulated 22.6 to 26.4 VAC

 

30 psig max  (PTP 3 to 30)
-7.5 psig max (PTP 0 to -7.5)

Supply Current

50 mA max @ 24 VDC

Accuracy

1% of full scale

Input Ranges

-7.5 to 0, 3 to 15 or 3 to 30 psig

Operating Temp.

32 to 120oF

Analog Outputs

1-5, 2-10, 3-15 VDC or 4-20 mA

Operating RH

10 to 95% RH non-condensing

Load Impedance

750 Ohms max  (Current Output)

Size

3.75” L x 2.25” W x 1.5” H

Dimensions

Ordering Information

Pressure Range Gauge Enclosure
ACI/PTP [  ] [  ] [  ]
     
(1) 3 to 15 psig (  ) No Gauge ( ) No Enclosure
(2) 3 to 30 psig (G) With Gauge (ENC) With Enclosure
(3) -7.5 to 0 psig

Example: A/PTP-(1)-(G)-(ENC)   or A/PTP-(2)  or A/PTP

Click here to View the PDF Version of this page